Description
The model GIR-10 gas presence detector uses non-dispersive infrared (NDIR) absorption spectroscopy at 947 cm⁻¹ to locate and quantify even minute SF6 leakages in high- and medium-voltage installations. Because it measures optical absorption specific to SF6, it is insensitive to ambient humidity and common volatile organic compounds (VOCs) and requires no consumables.
Both the shoulder-worn console case and the ergonomic gooseneck hand-held probe feature clear digital readouts so technicians can read live values from any position. Any background concentration can be tared to 0 ppmv so readings above zero immediately indicate a leak, supported by visual and audible alarms.
Functions & features
Key features
- Non-dispersive infrared (NDIR) measurement at 947 cm⁻¹ with no consumables and maintenance-free operation within the calibration cycle
- Detects concentrations down to 0.6 ppmv (integral leak test version) or 3 ppmv with < 1 second T90 response time (leakage detection version)
- Selective to SF6 with zero cross-sensitivity to VOCs and no humidity influence (0 to 95 % r.h., non-condensing)
- Dual digital indicators on both the console case and movable gooseneck probe, plus tare-to-zero background offset
- Visual and audible alarm thresholds (SF6 versions) and exchangeable particle filter protecting the optical cell
- Factory-calibrated with certified test gases; rechargeable Li-ion battery delivering approx. 8 hours of field operation
Technical highlights
- Calibration cycle: after 1,200 operating hours or every 2 years at the latest
- Battery charger: AC 100 to 265 V, 50/60 Hz; operating temperature 0 to 50 °C (storage -10 to +60 °C)
- Console dimensions & weight: 285 × 195 × 80 mm, 2.5 kg
- Hand-held probe dimensions & weight: 210 × 110 × 90 mm (gooseneck 250 mm or 600 mm), 0.5 kg
Applications
Industry
HV asset application
Typical applications
- Pinpointing and quantifying SF6 leaks on live switchgear joints, valves and flanges
- Integral leak-rate determination during factory final inspection of SF6-filled plants
- CO2 integral leak testing on clean-air / dry-air insulated switchgear
Packages & variants
Hardware packages
Variants

SF6 (0 ... 2,000 ppmv)
Leakage detection: 3 ppmv limit, 3 g/year (1.81 × 10⁻⁵ mbar·L/s), < 1 s T90, ppmv / g/y / cc/s, visual & audible alarm

SF6 (0 ... 50 ppmv)
Integral leak test: 0.6 ppmv limit, 0.34 g/year (1.81 × 10⁻⁶ mbar·L/s), 0.1 ppmv resolution, < 12 s T90, visual & audible alarm

CO2 (0 ... 1,000 ppmv)
Integral leak test for N2/Clean Air/dry air: 10 ppmv limit, 3.43 g/year, < 1 s T90, visual alarm