WIKA GA11 portable SF6 and alternative gas analyser in field case

Gas Analysis

GA11 Gas Analyser for SF6 and Alternative Gases

Model GA11

Portable V2025 multi-gas analytic instrument measuring purity, humidity and up to six decomposition products in SF6, C4-FN mixtures and natural origin gases with zero-emission pump-back.

Request a Quote

Documentation

Description

The WIKA model GA11 (V2025) is a field-ready multi-gas analytic instrument for assessing the quality of SF6 as well as modern eco-efficient alternative insulating gases, including C4-FN gas mixtures and natural origin gases (NOG based on N2, O2 and CO2). Depending on the selected sensor configuration, it simultaneously measures up to six parameters including purity, moisture and decomposition products.

Engineered around a closed, zero-emission gas loop, the GA11 temporarily stores sampled gas in an internal depot and pumps it directly back into the switchgear compartment (up to 10 bar abs.) or into an external GA45 gas recovery bag. Its 10" colour touchscreen, intelligent stability-based automatic measurement termination, battery/mains operation and wheeled IP67 hard-top case make it ideal for substation fieldwork without IATA air-transport restrictions.

Functions & features

Key features

  • Analyses SF6, C4-FN gas mixtures (CO2/N2 matrix) and natural origin gases (NOG) with up to six simultaneous substance measurements
  • Closed zero-emission design with internal gas depot for direct pump-back (up to 10 bar abs.) or recovery into an external GA45 bag
  • Intelligent automatic mode terminates measurement once sensor stability criteria are reached
  • 10" colour TFT touchscreen with intuitive menu navigation, audio cues and USB data export
  • Full functionality on both NiMH rechargeable battery (DC 21.6 V, 3 Ah) and AC 110–240 V mains power
  • Not subject to IATA air-transport restrictions; rugged wheeled IP67 closed field case (58 × 47 × 30 cm, approx. 22–22.5 kg)

Sensing technology & specifications

  • Purity (speed-of-sound sensor): SF6/N2 (80–100 % ±0.2 vol. %, 50–80 % ±0.3 vol. %) & switchable SF6/CF4 (±0.5 vol. %); C4-FN/CO2 or N2 (0–15 % ±0.2 vol. %); NOG CO2/N2 (±1.5 vol. %), SF6/N2 or He/N2
  • Humidity (polymer capacitive sensor): -40 to +40 °C (±2 K) and -60 to < -40 °C (±3 K); 0.01 °C resolution; displays °C Td,atm, °C Tf/d,atm, °C Td,press, ppmw, ppmv and % rH
  • Optional SF6 decomposition sensors: SO2 (0–20 / 0–100 / 0–500 ppm), HF (0–10 ppm ±0.4 ppm), H2S (0–100 ppm ±2 ppm), CO (0–500 ppm ±10 ppm)
  • Optional C4-FN & NOG sensors: optical O2 (0–25 % ±0.3 vol. %, 5-year service life), CO (0–500 / 2,000 / 10,000 / 40,000 ppm), NO2 (0–20 ppm ±1 ppm)
  • Inlet pressure: 1.03 to 16 bar abs. direct (up to 35 bar abs. with optional pressure reducer); measuring gas flow rate 18 L/h; 2-year calibration interval

Applications

Industry

  • Transmission & distribution utilities
  • Power generation
  • Equipment manufacturers (OEM)
  • Testing & service providers

HV asset application

  • Gas-insulated switchgear (GIS)
  • Circuit breakers
  • Instrument transformers (CT/VT)
  • SF6 gas

Typical applications

  • On-site purity, dew point and decomposition product analysis of SF6 switchgear
  • Commissioning and periodic diagnostics of C4-FN and natural origin gas (NOG) equipment
  • Zero-emission gas quality compliance verification to IEC 60480 and CIGRE guidelines

Packages & variants

Hardware packages

Variants

  • SF6 Version

    SF6/N2 or switchable SF6/CF4 purity + H2O with selectable SO2, HF, H2S and CO sensors

  • C4-FN Version

    C4-FN/CO2 or switchable C4-FN/N2 purity + H2O + optical O2 with selectable CO range (500 to 40,000 ppm)

  • NOG Version

    CO2/N2 or SF6/N2 + He/N2 purity + H2O + optical O2 with selectable CO and NO2 sensors