Description
DIRANA uses dielectric frequency response (DFR) analysis to judge the condition of high-voltage insulation. It determines the moisture content of cellulose insulation without oil sampling, for cellulose in mineral oil, natural and synthetic esters, air or vacuum, and classifies the results automatically according to IEC 60422.
Typical test objects are power and instrument transformers and bushings, and it also handles rotating machines, RBP, RIP and RIS bushings and power cables. One measurement additionally yields power/dissipation factor at line frequency, capacitance, insulation resistance, polarization index (PI) and dielectric absorption ratio (DAR).
Functions & features
Benefits
- Combines Frequency Domain Spectroscopy (FDS) with an advanced Polarization and Depolarization Current (PDC+) method, reaching ultra-low frequencies below 0.1 Hz.
- Up to 20× faster testing, with a full 10 µHz - 1 kHz sweep in under 2 hours.
- Fully automatic parameter setting and improved moisture assessment.
- Guided setup, execution and assessment that needs no expert knowledge.
- Light, rugged test set for field use (19 kg / 42 lbs).
Guided Testing With Primary Test Manager
DIRANA is operated with Primary Test Manager (PTM), which generates test plans from nameplate data and international standards, evaluates results against standard or custom limits and handles data management and reporting. The PTMate app adds data entry and wiring diagrams on a smartphone.