Description
CMC CT-Check automates basic current transformer checks on the CMC 500: voltage-based ratio, polarity, temperature-corrected winding resistance, knee-point voltage (up to 2.5 kV, per IEC 61869-2) and operating burden. The CT is demagnetized automatically afterwards.
This helps catch polarity, ratio, core connection, burden and remanence problems quickly.
Functions & features
Benefits
- Detects issues commonly caused by incorrect core connection, polarity inversion, undocumented burden changes and residual magnetization.
- One test set for both relay tests and functional CT tests.
- Minimal rewiring with guided steps and monitored residual current for safe testing.
- A one-page commissioning report.
Characteristics
- Separate CMC CT-Check license
- Requires a CMC 500 with analog input option
- Knee-point determination up to 2.5 kV
- IEC 61869-2 knee-point definition
- Automatic demagnetization
- One-page report
Applications
Industry
HV asset application