Description
The MI 3290 Earth Analyser is a portable instrument powered by battery or mains, rated IP 54 with the case open. It measures earth resistance, specific earth resistance and earth potential on both energy and non-energy installations.
Methods range from classic 3-wire earth resistance up to one- and four-clamp measurements on pylons, using a single frequency, a frequency sweep from 55 Hz to 15 kHz, an HF method at 25 kHz or a pulse method that simulates a lightning strike. High noise immunity suits it to industrial sites. It is offered in several sets that combine different accessories and measuring functions.
Functions & features
Measuring functions
- Earth Resistance 2,3,4 -pole
- Specific Earth Resistance (Wenner and Schlumberger method)
- Low Ohm measurement 7 mA and 200 mA
- Earth Potential
- Step and contact measurements.
Key features
- Many types of earth measurement with one instrument.
- Earth impedance analysed against frequency over a wide 55 Hz … 15 kHz band, with an on-screen Z(f) sweep.
- Earth measurements on pylons with the protective earth cable still connected.
- DC resistance measurement.
- 4.3" high-resolution colour touch screen.
- Floating universal mains supply (90 … 260 V AC) or battery power with a built-in fast charger.
- IP 65 with the case closed, IP 54 open.
- Checkbox with several self-check methods.
- Single or automated measurements.
- PC software for preparing test structures, downloading results and viewing, storing and printing them in tree, table and graph views.
Applications
Industry
HV asset application
Typical applications
- Power generation: Earthing and lightning protection in thermal energy power plants
- Renewable energy sources: Generator stator testing; STC values and performance of PV panels; Lightning protection testing in wind plants; Fall of potential method for solar and wind stations
- Power distribution: Step and touch voltages of transformers; Earth resistance measurement and 62% rule
- Industrial installations: Specific earth resistance measurement methods
- Low voltage earthing and lightning protection: Earthing measurement with fall of potential method
- Hospital earthing and lightning protection: Hospital earthing measurement with fall of potential method