Description
Manufactured since 1966 to the design of English Electric, UK.
Type tested to IEC 60214 and IS 8468.
Voltage ratings (Um) from 12 kV to 145 kV for delta and star application, with current ratings up to 600 A in 9, 17 and 21 and up to 33 positions.
Compatible with SCADA and modern data communication equipment and systems.
Applications
Industry
HV asset application
Typical applications
- The 11 kV to 33 kV compact 8- and 16-step types serve distribution transformers, where the regulation band is limited or fine regulation is needed.
- EN16, EN20, EQ16 and FQ16 also suit furnace duty with a large number of operations; EQ16 is meant for high-current applications.
- The 66 kV and 132 kV types serve transmission and network transformers to maintain grid voltage; GQ16 is used at the neutral end of star-connected windings.
- IUZE is the only flange-mounted type suitable for 132 kV delta application and works with linear, coarse-fine and reversing windings.
Packages & variants
Variants

CB16
11 kV 17 position linear 200 A

CL08
11 kV 9 position linear 300 A

CM08
11 kV 9 position linear 200 A

CM16
11 kV 17 position linear 200 A

DB16
22 kV 17 position linear 200 A

DM08
22 kV 9 position linear 300 A

DM16
22 kV 17 position linear 300 A

EL08
33 kV 9 position linear 300 A

EN16
33 kV 17 position linear 300 A; Legacy product manufactured to English Electric design.

EN20
33 kV 21 position linear 300 A

EO09
33 kV 10 position linear 300 A

EO16
33 kV 17 position 300 A tapchanger with changeover selector.

EQ16
33 kV 17 position linear 500 A

FQ16
66 kV 17 position linear 300 A; Legacy product manufactured to English Electric design.

FR16
66 kV 17 position linear 300 A

FR20
66 kV 21 position linear 300 A

GQ16
132 kV 17 position linear 300 A

IUZE
Selector switch type external/flange mounted; Voltage rating from 33 to 132 kV and current rating upto 600 A.